N2XS(F)2Y 10kV
According to VDE 0276 part 620.
- Variants
- Downloads
- Shorter and longer lengths
-
Number of cores
Cross section conductor
Technical features Product N2XS(F)2Y 10kV 1X35 RM/16 10kV 1 35 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 35 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 25 mm
- Min. permitted bending radius, stationary application/permanent installation
- 375 mm
- Weight
- 762.08 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 275779 Cut length Ring, Drum N2XS(F)2Y 10kV 1X50 RM/16 10kV 1 50 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 50 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 26 mm
- Min. permitted bending radius, stationary application/permanent installation
- 390 mm
- Weight
- 889.57 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 233748 Cut length Ring, Drum N2XS(F)2Y 10kV 1X70 RM/16 10kV 1 70 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 70 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 28 mm
- Min. permitted bending radius, stationary application/permanent installation
- 420 mm
- Weight
- 1,105.6 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 233779 Cut length Ring, Drum N2XS(F)2Y 10kV 1X95 RM/16 10kV 1 95 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 95 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 29 mm
- Min. permitted bending radius, stationary application/permanent installation
- 450 mm
- Weight
- 1,359.05 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 233809 Cut length Ring, Drum N2XS(F)2Y 10kV 1X120 RM/16 10kV 1 120 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 120 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 31 mm
- Min. permitted bending radius, stationary application/permanent installation
- 465 mm
- Weight
- 1,602.3 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 233823 Cut length Ring, Drum N2XS(F)2Y 10kV 1X150 RM/25 10kV 1 150 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 150 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 32 mm
- Min. permitted bending radius, stationary application/permanent installation
- 495 mm
- Weight
- 1,958.7 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 233854 Cut length Ring, Drum N2XS(F)2Y 10kV 1X185 RM/25 10kV 1 185 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 185 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Nominal cross section concentric conductor
- 25 mm²
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 33 mm
- Min. permitted bending radius, stationary application/permanent installation
- 510 mm
- Weight
- 2,296.3 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 233885 Cut length Ring, Drum N2XS(F)2Y 10kV 1X240 RM/25 10kV 1 240 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 240 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 37 mm
- Min. permitted bending radius, stationary application/permanent installation
- 555 mm
- Weight
- 2,844.73 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 218813 Cut length Ring, Drum N2XS(F)2Y 10kV 1X300 RM/25 10kV 1 300 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 300 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 38 mm
- Weight
- 3,407.8 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 608171 Cut length Ring, Drum N2XS(F)2Y 10kV 1X400 RM/35 10kV 1 400 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 400 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 41 mm
- Min. permitted bending radius, stationary application/permanent installation
- 630 mm
- Weight
- 4,288.9 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 292424 Cut length Ring, Drum N2XS(F)2Y 10kV 1X500 RM/35 10kV 1 500 mm² - Conductor material
- Copper
- Conductor surface
- Bare
- Nominal cross section conductor
- 500 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 45 mm
- Min. permitted bending radius, stationary application/permanent installation
- 675 mm
- Weight
- 5,316.8 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 292264 Cut length Ring, Drum -
We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.
To shorter and longer lengths "N2XS(F)2Y 10kV"
If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.