NA2XS(F)2Y (3x) 20kV

Mittelspannungskabel, VPE-isoliert mit Al-Leiter, längswasserdichtem Schirm und PE-Mantel

NA2XS(F)2Y (3x) 20kV

According to VDE 0276 part 620.

  • Variants
  • Downloads
  • Shorter and longer lengths
  • Number of cores

    Cross section conductor

    Technical features Product
    NA2XS(F)2Y (3x) 20kV 3X1X150 RM/25 20kV 3 150 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    150 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification according to HD 308 S2
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Nominal cross section concentric conductor
    25 mm²
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    Yes
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    76 mm
    Min. permitted bending radius, stationary application/permanent installation
    1,170 mm
    Weight
    3,812.9 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    12 kV
    Nominal voltage U
    20 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    295388 Cut length Ring, Drum
    NA2XS(F)2Y (3x) 20kV 3X1X150 RE/25 20kV 3 150 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    150 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification according to HD 308 S2
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Nominal cross section concentric conductor
    25 mm²
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    Yes
    Longitudinal water blocking screen
    Yes
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    74 mm
    Weight
    3,730.8 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    12 kV
    Nominal voltage U
    20 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    421930 Cut length Ring, Drum
    NA2XS(F)2Y (3x) 20kV 3X1X240 RM/25 20kV 3 240 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    240 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification according to HD 308 S2
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    Yes
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    85 mm
    Min. permitted bending radius, stationary application/permanent installation
    1,305 mm
    Weight
    4,899.5 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    12 kV
    Nominal voltage U
    20 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    294602 Cut length Ring, Drum
    NA2XS(F)2Y (3x) 20kV 3X1X300 RM/25 20kV 3 300 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    300 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification according to HD 308 S2
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Nominal cross section concentric conductor
    25 mm²
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    Yes
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    90 mm
    Min. permitted bending radius, stationary application/permanent installation
    1,380 mm
    Weight
    5,569.7 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    12 kV
    Nominal voltage U
    20 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    269525 Cut length Ring, Drum
  • Title Language
    Datasheet
    Declaration of Performance
  • We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.

    If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.

    To shorter and longer lengths "NA2XS(F)2Y (3x) 20kV"