Number of cores
Cross section conductor
Technical features Product NA2XS2Y 30kV 1X50 RM/16 30kV 1 50 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 50 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 34 mm
- Min. permitted bending radius, stationary application/permanent installation
- 525 mm
- Weight
- 961.63 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235520 Cut length Ring, Drum NA2XS2Y 30kV 1X70 RM/16 30kV 1 70 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 70 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 36 mm
- Min. permitted bending radius, stationary application/permanent installation
- 555 mm
- Weight
- 1,068 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235551 Cut length Ring, Drum NA2XS2Y 30kV 1X95 RM/16 30kV 1 95 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 95 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 38 mm
- Min. permitted bending radius, stationary application/permanent installation
- 585 mm
- Weight
- 1,217.6 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235582 Cut length Ring, Drum NA2XS2Y 30kV 1X120 RM/16 30kV 1 120 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 120 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 39 mm
- Min. permitted bending radius, stationary application/permanent installation
- 600 mm
- Weight
- 1,332.7 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235612 Cut length Ring, Drum NA2XS2Y 30kV 1X150 RM/25 30kV 1 150 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 150 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 41 mm
- Min. permitted bending radius, stationary application/permanent installation
- 630 mm
- Weight
- 1,511.1 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235636 Cut length Ring, Drum NA2XS2Y 30kV 1X185 RM/25 30kV 1 185 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 185 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 43 mm
- Min. permitted bending radius, stationary application/permanent installation
- 645 mm
- Weight
- 1,675.3 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235667 Cut length Ring, Drum NA2XS2Y 30kV 1X240 RM/25 30kV 1 240 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 240 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 45 mm
- Min. permitted bending radius, stationary application/permanent installation
- 690 mm
- Weight
- 1,897.6 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 235698 Cut length Ring, Drum NA2XS2Y 30kV 1X300 RM/25 30kV 1 300 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 300 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 48 mm
- Weight
- 2,144.9 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 694624 Cut length Ring, Drum NA2XS2Y 30kV 1X400 RM/35 30kV 1 400 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 400 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 1 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 51 mm
- Min. permitted bending radius, stationary application/permanent installation
- 765 mm
- Weight
- 2,568.3 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 18 kV
- Nominal voltage U
- 30 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 295883 Cut length Ring, Drum -
We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.
To shorter and longer lengths "NA2XS2Y 30kV"