NA2XS2Y 30kV

Medium-voltage cable, XLPE insulated, aluminum conductor, polyethylene outershe

NA2XS2Y 30kV

According to VDE 0276 part 620.

  • Variants
  • Downloads
  • Shorter and longer lengths
  • Number of cores

    Cross section conductor

    Technical features Product
    NA2XS2Y 30kV 1X50 RM/16 30kV 1 50 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    50 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    34 mm
    Min. permitted bending radius, stationary application/permanent installation
    525 mm
    Weight
    961.63 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235520 Cut length Ring, Drum
    NA2XS2Y 30kV 1X70 RM/16 30kV 1 70 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    70 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    36 mm
    Min. permitted bending radius, stationary application/permanent installation
    555 mm
    Weight
    1,068 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235551 Cut length Ring, Drum
    NA2XS2Y 30kV 1X95 RM/16 30kV 1 95 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    95 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    38 mm
    Min. permitted bending radius, stationary application/permanent installation
    585 mm
    Weight
    1,217.6 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235582 Cut length Ring, Drum
    NA2XS2Y 30kV 1X120 RM/16 30kV 1 120 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    120 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    39 mm
    Min. permitted bending radius, stationary application/permanent installation
    600 mm
    Weight
    1,332.7 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235612 Cut length Ring, Drum
    NA2XS2Y 30kV 1X150 RM/25 30kV 1 150 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    150 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    41 mm
    Min. permitted bending radius, stationary application/permanent installation
    630 mm
    Weight
    1,511.1 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235636 Cut length Ring, Drum
    NA2XS2Y 30kV 1X185 RM/25 30kV 1 185 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    185 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    43 mm
    Min. permitted bending radius, stationary application/permanent installation
    645 mm
    Weight
    1,675.3 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235667 Cut length Ring, Drum
    NA2XS2Y 30kV 1X240 RM/25 30kV 1 240 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    240 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    45 mm
    Min. permitted bending radius, stationary application/permanent installation
    690 mm
    Weight
    1,897.6 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    235698 Cut length Ring, Drum
    NA2XS2Y 30kV 1X300 RM/25 30kV 1 300 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    300 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    48 mm
    Weight
    2,144.9 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    694624 Cut length Ring, Drum
    NA2XS2Y 30kV 1X400 RM/35 30kV 1 400 mm²
    Conductor material
    Aluminium
    Conductor surface
    Bare
    Nominal cross section conductor
    400 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    1 Stck
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    51 mm
    Min. permitted bending radius, stationary application/permanent installation
    765 mm
    Weight
    2,568.3 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -20 <=> 70 °C
    Nominal voltage U0
    18 kV
    Nominal voltage U
    30 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    295883 Cut length Ring, Drum
  • Title Language
    Datasheet
    Declaration of Performance
  • We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.

    If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.

    To shorter and longer lengths "NA2XS2Y 30kV"