VG-YMvKas Dca

Starkstromkabel, VPE-isoliert mit Cu-Leitern und konz. Leiter aus Stahl- u. Cu-Drähten, mit verb. Verhalten im Brandfall

VG-YMvKas Dca

based upon HD 604 4D.

  • Variants
  • Downloads
  • Shorter and longer lengths
  • Number of cores

    Cross section conductor

    Technical features Product
    VG-YMvKas Dca Dca 2X4 RE/4 2 4 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    4 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    4 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    16 mm
    Min. permitted bending radius, stationary application/permanent installation
    192 mm
    Weight
    444.13 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    282814 Cut length Ring, Drum
    VG-YMvKas Dca Dca 3X10 RM/10 3 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    10 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    20 mm
    Min. permitted bending radius, stationary application/permanent installation
    228 mm
    Weight
    791.38 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    263387 Cut length Ring, Drum
    VG-YMvKas Dca Dca 3X10 RE/10 (EVU) 3 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    10 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    19 mm
    Weight
    766.8 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    496426 Cut length Ring, Drum
    VG-YMvKas Dca Dca 3X16 RM/16 3 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    22 mm
    Min. permitted bending radius, stationary application/permanent installation
    252 mm
    Weight
    1,059.7 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    263486 Cut length Ring, Drum
    VG-YMvKas Dca Dca 3X25 RM/16 3 25 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    25 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    25 mm
    Weight
    1,435.6 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    548927 Cut length Ring, Drum
    VG-YMvKas Dca Dca 3X35 SM/16 3 35 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    35 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    25 mm
    Weight
    1,599.1 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    742981 Cut length Ring, Drum
    VG-YMvKas Dca Dca 3X185 SM/95 3 185 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    185 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    95 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    48 mm
    Weight
    7,386 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    743797 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X10 RM/10 4 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification according to HD 308 S2
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    10 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    21 mm
    Min. permitted bending radius, stationary application/permanent installation
    252 mm
    Weight
    936.4 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    263431 Cut length Ring, Drum
    822461 100 m 100 Drum
    805990 500 m 500 Drum
    VG-YMvKas Dca Dca 4X16 RM/16 4 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification according to HD 308 S2
    Yes
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    23 mm
    Min. permitted bending radius, stationary application/permanent installation
    276 mm
    Weight
    1,265.2 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    263530 Cut length Ring, Drum
    806027 500 m 500 Drum
    VG-YMvKas Dca Dca 4X16 RM/16 (EVU) 4 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification according to HD 308 S2
    Yes
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    25 mm
    Weight
    1,339.9 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    459834 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X25 RM/16 4 25 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    25 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    28 mm
    Weight
    1,774.5 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    547395 Cut length Ring, Drum
    806034 500 m 500 Drum
    VG-YMvKas Dca Dca 4X35 SM/16 4 35 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    35 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    16 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    28 mm
    Weight
    2,074.9 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    570867 Cut length Ring, Drum
    806041 500 m 500 Drum
    VG-YMvKas Dca Dca 4X50 SM/25 4 50 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    50 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    25 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    33 mm
    Weight
    2,796.8 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    509911 Cut length Ring, Drum
    806058 500 m 500 Drum
    VG-YMvKas Dca Dca 4X70 SM/35 4 70 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    70 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    35 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    36 mm
    Weight
    3,664.9 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    554652 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X95 SM/50 4 95 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    95 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    50 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    40 mm
    Weight
    4,830.6 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    554713 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X120 SM/60 4 120 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    120 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    60 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    45 mm
    Weight
    6,062.9 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    554782 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X150 SM/75 4 150 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    150 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification according to HD 308 S2
    Yes
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    75 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    47 mm
    Weight
    7,200.8 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    554850 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X185 SM/95 4 185 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    185 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification according to HD 308 S2
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    95 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    55 mm
    Weight
    9,604.3 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    554911 Cut length Ring, Drum
    VG-YMvKas Dca Dca 4X240SM/120 4 240 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    240 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Sector-shaped
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    Other
    Nominal cross section concentric conductor
    120 mm²
    Armouring
    Yes
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    60 mm
    Weight
    12,090 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    505548 Cut length Ring, Drum
  • Title Language
    Datasheet
    Declaration of Performance
  • We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.

    If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.

    To shorter and longer lengths "VG-YMvKas Dca"