NA2XS(F)2Y (3x) 10kV
According to VDE 0276 part 620.
- Variants
- Downloads
- Shorter and longer lengths
-
Number of cores
Cross section conductor
Technical features Product NA2XS(F)2Y (3x) 10kV 3X1X150 RM/25 10kV 3 150 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 150 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 3 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 67 mm
- Min. permitted bending radius, stationary application/permanent installation
- 1,035 mm
- Weight
- 3,253.35 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 242412 Cut length Ring, Drum NA2XS(F)2Y (3x) 10kV 3X1X185 RM/25 10kV 3 185 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 185 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 3 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 71 mm
- Min. permitted bending radius, stationary application/permanent installation
- 1,110 mm
- Weight
- 3,672.3 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 313822 Cut length Ring, Drum NA2XS(F)2Y (3x) 10kV 3X1X240 RM/25 10kV 3 240 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 240 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 3 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 76 mm
- Min. permitted bending radius, stationary application/permanent installation
- 1,170 mm
- Weight
- 4,263.9 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 242450 Cut length Ring, Drum NA2XS(F)2Y (3x) 10kV 3X1X240 RE/25 10kV 3 240 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 240 mm²
- Conductor category
- Class 1 = solid
- Shape of conductor
- Round
- Number of cores
- 3 Stck
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Conductive coating
- No
- Longitudinal water blocking conductors
- Yes
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 73 mm
- Min. permitted bending radius, stationary application/permanent installation
- 1,125 mm
- Weight
- 4,155 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 303960 Cut length Ring, Drum NA2XS(F)2Y (3x) 10kV 3X1X500 RM/35 10kV 3 500 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 500 mm²
- Conductor category
- Class 2 = stranded
- Shape of conductor
- Round
- Number of cores
- 3 Stck
- Core identification according to HD 308 S2
- Core identification
- None
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- Yes
- Outer semi-conducting layer
- Yes
- Screen
- Yes
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Black
- Cable geometry
- Conductive coating
- No
- Longitudinal water blocking conductors
- No
- Longitudinal water blocking screen
- Yes
- Reaction-to-fire according to EN 13501-6: Class
- Fca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- No
- Low smoke (acc. EN 61034-2)
- No
- Outer diameter approx.
- 94 mm
- Weight
- 7,069.7 kg/km
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -20 <=> 70 °C
- Nominal voltage U0
- 6 kV
- Nominal voltage U
- 10 kV
- Suitable as installation cable
- Certified for shipboard application
- Suitable as medium-voltage cable
- Suitable as high-voltage cable
- Certified as airport lighting cable
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 15 x Außen-Ø
Product No. Individual length Pallet unit Packing 496594 Cut length Ring, Drum -
We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.
To shorter and longer lengths "NA2XS(F)2Y (3x) 10kV"
If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.