YMvK Dca

Power cable, XLPE insulated, copper conductor, improved behavior in case of fire

YMvK Dca

according HD 604 4D.

  • Variants
  • Downloads
  • Shorter and longer lengths
  • Number of cores

    Cross section conductor

    Technical features Product
    YMvK Dca Dca 2X1,5 RE 2 1.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    1.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    10 mm
    Min. permitted bending radius, stationary application/permanent installation
    100 mm
    Weight
    131.36 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Paletteinheit
    4,200 m
    Bruttogewicht pro Paletteinheit
    574.51 kg
    Product No. Individual length Pallet unit Packing
    282364 100 m 4,200 Ring
    262144 500 m 5,000 Drum
    YMvK Dca Dca 2X2,5 RE 2 2.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    2.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    11 mm
    Min. permitted bending radius, stationary application/permanent installation
    110 mm
    Weight
    162.54 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Paletteinheit
    3,600 m
    Außendurchmesser
    390 mm
    Kerndurchmesser
    200 mm
    Höhe
    122 mm
    Bruttogewicht pro Paletteinheit
    607.94 kg
    Product No. Individual length Pallet unit Packing
    282371 100 m 3,600 Ring
    262175 500 m 2,000 Drum
    YMvK Dca Dca 2x4 RE 2 4 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    4 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    12 mm
    Weight
    206.94 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    595136 Cut length Ring, Drum
    YMvK Dca Dca 2X6 RE 2 6 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    6 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    13 mm
    Weight
    261.54 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    595167 Cut length Ring, Drum
    YMvK Dca Dca 2X10 RM 2 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    15 mm
    Weight
    385.74 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    595259 Cut length Ring, Drum
    YMvK Dca Dca 2X16 RM 2 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    2 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    17 mm
    Weight
    540.16 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    595280 Cut length Ring, Drum
    YMvK Dca Dca 3G1,5 RE 3 1.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    1.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    10 mm
    Min. permitted bending radius, stationary application/permanent installation
    100 mm
    Weight
    148.2 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    326600 Cut length Ring, Drum
    815852 25 m 2,250 Ring
    262205 100 m 4,200 Ring
    282036 500 m 5,000 Drum
    YMvK Dca Dca 3G2,5 RE 3 2.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    2.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    11 mm
    Weight
    187.55 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    333714 Cut length Ring, Drum
    639182 50 m 3,300 Ring
    262236 100 m 3,000 Ring
    282043 500 m 2,000 Drum
    547500 1000 m 4,000 Drum
    YMvK Dca Dca 3G4 RE 3 4 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    4 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    12 mm
    Weight
    244.33 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    441006 Cut length Ring, Drum
    440962 100 m 3,000 Ring
    440993 500 m 2,000 Drum
    YMvK Dca Dca 3G6 RE 3 6 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    6 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    13 mm
    Weight
    315.1 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    594757 Cut length Ring, Drum
    685929 100 m 1,600 Ring
    766741 500 m 2,000 Drum
    YMvK Dca Dca 3G10 RM 3 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    16 mm
    Weight
    472.66 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    594788 Cut length Ring, Drum
    YMvK Dca Dca 3G16 RM 3 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    18 mm
    Weight
    675.02 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    594832 Cut length Ring, Drum
    YMvK Dca Dca 4G1,5 RE 4 1.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    1.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    11 mm
    Min. permitted bending radius, stationary application/permanent installation
    110 mm
    Weight
    172.3 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Paletteinheit
    3,000 m
    Außendurchmesser
    390 mm
    Kerndurchmesser
    200 mm
    Höhe
    130 mm
    Bruttogewicht pro Paletteinheit
    537.45 kg
    Product No. Individual length Pallet unit Packing
    262267 100 m 3,000 Ring
    282050 500 m 2,000 Drum
    YMvK Dca Dca 4G2,5 RE 4 2.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    2.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    12 mm
    Min. permitted bending radius, stationary application/permanent installation
    120 mm
    Weight
    221.78 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262298 Cut length Ring, Drum
    766710 100 m 2,400 Ring
    310913 500 m 2,000 Drum
    YMvK Dca Dca 4G2,5 RE (GG/SW/BL/BR 4 2.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    2.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    12 mm
    Weight
    221.78 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    581771 Cut length Ring, Drum
    YMvK Dca Dca 4G4 RE 4 4 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    4 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    13 mm
    Min. permitted bending radius, stationary application/permanent installation
    130 mm
    Weight
    293.59 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262328 Cut length Ring, Drum
    277940 50 m 2,400 Ring
    277957 100 m 2,000 Ring
    766727 500 m 2,000 Drum
    YMvK Dca Dca 4G4 RE (GG/SW/BL/BR) 4 4 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    4 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    13 mm
    Min. permitted bending radius, stationary application/permanent installation
    156 mm
    Weight
    293.57 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Paletteinheit
    2,000 m
    Bruttogewicht pro Paletteinheit
    609.94 kg
    Product No. Individual length Pallet unit Packing
    777709 100 m 2,000 Ring
    197378 500 m 2,000 Drum
    YMvK Dca Dca 4G6 RE (GG/SW/BL/BR) 4 6 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    6 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    14 mm
    Min. permitted bending radius, stationary application/permanent installation
    168 mm
    Weight
    383.38 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    197385 Cut length Ring, Drum
    YMvK Dca Dca 4G6 RE 4 6 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    6 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    14 mm
    Min. permitted bending radius, stationary application/permanent installation
    140 mm
    Weight
    383.38 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262359 Cut length Ring, Drum
    277964 50 m 1,200 Ring
    277971 100 m 1,600 Ring
    YMvK Dca Dca 4X6 RE 4 6 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    6 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    14 mm
    Weight
    383.38 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Paletteinheit
    2,000 m
    Außendurchmesser
    752 mm
    Kerndurchmesser
    315 mm
    Höhe
    419 mm
    Bruttogewicht pro Paletteinheit
    840.2 kg
    Product No. Individual length Pallet unit Packing
    662876 500 m 2,000 Drum
    YMvK Dca Dca 4G10 RM 4 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    17 mm
    Weight
    582.03 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    512607 Cut length Ring, Drum
    807901 Cut length Ring, Drum
    YMvK Dca Dca 4G10 RM (GG/SW/BL/BR) 4 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    17 mm
    Weight
    583.18 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    661534 Cut length Ring, Drum
    YMvK Dca Dca 4G16 RM (GG/SW/BL/BR) 4 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    19 mm
    Min. permitted bending radius, stationary application/permanent installation
    228 mm
    Weight
    840.73 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    12 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    197408 Cut length Ring, Drum
    YMvK Dca Dca 4G16 RM 4 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    4 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    19 mm
    Min. permitted bending radius, stationary application/permanent installation
    190 mm
    Weight
    840.73 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262427 Cut length Ring, Drum
    278008 50 m 900 Ring
    YMvK Dca Dca 5G1,5 RE 5 1.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    1.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    5 Stck
    Core identification according to HD 308 S2
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    12 mm
    Min. permitted bending radius, stationary application/permanent installation
    120 mm
    Weight
    199.7 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Paletteinheit
    3,000 m
    Außendurchmesser
    390 mm
    Kerndurchmesser
    200 mm
    Höhe
    149 mm
    Bruttogewicht pro Paletteinheit
    621.9 kg
    Product No. Individual length Pallet unit Packing
    262502 100 m 3,000 Ring
    310814 500 m 2,000 Drum
    YMvK Dca Dca 5G2,5 RE 5 2.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    2.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    5 Stck
    Core identification according to HD 308 S2
    Yes
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    13 mm
    Min. permitted bending radius, stationary application/permanent installation
    130 mm
    Weight
    255.5 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262533 Cut length Ring, Drum
    779901 50 m 3,000 Ring
    639205 100 m 2,400 Ring
    639212 500 m 2,000 Drum
    YMvK Dca Dca 5G4 RE 5 4 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    4 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    5 Stck
    Core identification according to HD 308 S2
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    14 mm
    Min. permitted bending radius, stationary application/permanent installation
    140 mm
    Weight
    347.66 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262564 Cut length Ring, Drum
    278015 50 m 1,200 Ring
    278022 100 m 1,600 Ring
    310869 500 m 2,000 Drum
    YMvK Dca Dca 5G6 RE 5 6 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    6 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    5 Stck
    Core identification according to HD 308 S2
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Cable geometry
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    15 mm
    Min. permitted bending radius, stationary application/permanent installation
    150 mm
    Weight
    456.94 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    Suitable as installation cable
    Certified for shipboard application
    Suitable as medium-voltage cable
    Suitable as high-voltage cable
    Certified as airport lighting cable
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262595 Cut length Ring, Drum
    278039 50 m 1,000 Ring
    278046 100 m 1,400 Ring
    766734 500 m 2,000 Drum
    YMvK Dca Dca 5G10 RM 5 10 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    10 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    5 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    18 mm
    Weight
    700.29 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    511051 Cut length Ring, Drum
    807888 Cut length Ring, Drum
    822454 100 m 400 Drum
    806072 500 m 500 Drum
    YMvK Dca Dca 5G16 RM 5 16 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    16 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    5 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    21 mm
    Min. permitted bending radius, stationary application/permanent installation
    210 mm
    Weight
    1,020 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    262663 Cut length Ring, Drum
    806065 500 m 500 Drum
    YMvK Dca Dca 7G1,5 RE 7 1.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    1.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    7 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    13 mm
    Min. permitted bending radius, stationary application/permanent installation
    130 mm
    Weight
    237.72 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    251452 Cut length Ring, Drum
    310685 500 m 2,000 Drum
    YMvK Dca Dca 7G2,5 RE 7 2.5 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    2.5 mm²
    Conductor category
    Class 1 = solid
    Shape of conductor
    Round
    Number of cores
    7 Stck
    Core identification
    Colour
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    Yes
    Inner semi-conducting layer
    No
    Outer semi-conducting layer
    No
    Screen
    No
    Concentric conductor
    None
    Armouring
    No
    Material outer sheath
    Polyvinyl chloride (PVC)
    Specification material outer sheath
    Other
    Colour outer sheath
    Grey
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Dca
    Reaction-to-fire according to EN 13501-6: Smoke production
    s2
    Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    d2
    Reaction-to-fire according to EN 13501-6: Acidity
    a3
    Halogen free (acc. EN 60754-1/2)
    No
    Flame retardant
    In accordance with IEC/EN 60332-3-24
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    14 mm
    Min. permitted bending radius, stationary application/permanent installation
    140 mm
    Weight
    315.48 kg/km
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    -5 <=> 70 °C
    Permitted cable outer temperature after assembling without vibration
    -30 <=> 70 °C
    Nominal voltage U0
    0.6 kV
    Nominal voltage U
    1 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    10 x Außen-Ø
    Product No. Individual length Pallet unit Packing
    251483 Cut length Ring, Drum
    310876 500 m 2,000 Drum
  • Title Language
    Datasheet
    Declaration of Performance
  • We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.

    If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.

    To shorter and longer lengths "YMvK Dca"